Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 10/19/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PULL PERMIT FOR WATER HEATER 2) WATER HEATER FLUE NOT PROPERLY INSTALLED 3) WATER HEATER T & P NOT PROPERLY TERMINATED 4) PROVIDE 6" CLEARANCE TO COMBUSTIBLES ON SINGLE WALL FLUE PIPING 5) UNABLE TO ACCESS ROOF |
|
| 10/15/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN 2) PLASTIC CONDENSATE PUMP NOT ALLOWED IN A RETURN PLENIUM 3) PROVIDE A TRAP ON CONDENSATE DRAIN 4) DO NOT TERMINATION CONDENSATE INTO A SEWER VENT 5) TERMINATE TO WITHIN 5" OF THE GROUND 6) NO PLASTIC HOSE TO BE EXPOSED OUTDOORS 7) IDENTIFY THE FUSE BANKS IN DISCONNECT OF ROOF 8) PULLING RED WIRE FOR GROUND THEN TAPING ENDS WITH GREEN TAPE IS UNACCEPTABLE 9) PROVIDE THE REQUIRED GREEN CONDUCTORS INTO DISCONNECT AND A/C UNIT |