Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/08/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SERVICE OUTLET 120V WITHIN 25' OF UNIT ON ROOF 2) BLOCKING SUPPORT ON PVC NOT TO EXCEED 4' SPACING 3) ALL DUCT WORK SUPPLY AND RETURN EXPOSED TO THE EXTERIOR TO HAVE A MINIMUM R-8 (2") DUCT LINER, THIS DUCT LINER APPEARS TO BE 1/2" REMOVE AND REPLACE |