Permit: T09ME00620

Parcel: 140152700


Addresses:

2052 E WEDWICK ST


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T09ME00620

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/20/2009 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/08/2009 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE SERVICE OUTLET 120V WITHIN 25' OF UNIT ON ROOF
2) BLOCKING SUPPORT ON PVC NOT TO EXCEED 4' SPACING
3) ALL DUCT WORK SUPPLY AND RETURN EXPOSED TO THE EXTERIOR TO HAVE A MINIMUM R-8 (2") DUCT LINER, THIS DUCT LINER APPEARS TO BE 1/2" REMOVE AND REPLACE