Permit: T09ME00617

Parcel: 133221210


Addresses:

7101 E KINGSTON DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/06/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/21/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A BUSGHIN AT PENETRATION INTO THE ELECTRIC DISCONNECT
2) TAPE BOTH ENDS OF WHITE WIRE WITH BLACK TAPE
3) PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE AT THE CONDENSOR
4) REMOVE THE PIECE OF SINGLE WALL VENT PIPE ON THE ROOF AND THE SINGLE WALL ELBOW OUTSIDE THE WALL AND PROVIDE DBL WALL VENT PIPE
5) PROVIDE MIN. 1" CLEARANCE FROM COMBUSTIBLES AT WALL PENETRATION