Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T09ME00612
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT PVC EVERY 4'. PAINT EXPOSED PVC WITH LATEX PAINT. USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE. SECURE TO BLOCKS 2) SUPPORT ELECTRIC CONDUITS ON ROOF 3) PROVIDE A MINIMUM 10 POUND PRESSURE TEST ON ALL NEW GAS PIPING 4) PROVIDE A FRESH AIR INTAKE WITH A FILTER 5) PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE ON ROOF 6) PROVIDE MINIMUM R8 DUCT INSULATION ON ALL EXPOSED DUCT ON THE ROOF |