Inspection History: MECHANICAL - FINAL
Permit Number - T09ME00576
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/22/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
09/15/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) SECURE AND SUPPORT CONDENSATE DRAIN LINE 2) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 3) DO NOT USE A VENT UPSTREAM OF THE TRAP 4) CONDENSOR NOT FUSED CORRECTLY 5) 40 AMP IS MAX 6) DO NOT USE DUCT TAPE OUTDOORS AT LINE SET 7) WATER HEATER INSTALLED WITHOUT PERMIT OR INSPECTION |