Inspection History: MECHANICAL - FINAL

Permit Number - T09ME00576

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/22/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
09/15/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) SECURE AND SUPPORT CONDENSATE DRAIN LINE
2) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
3) DO NOT USE A VENT UPSTREAM OF THE TRAP
4) CONDENSOR NOT FUSED CORRECTLY
5) 40 AMP IS MAX
6) DO NOT USE DUCT TAPE OUTDOORS AT LINE SET
7) WATER HEATER INSTALLED WITHOUT PERMIT OR INSPECTION