Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/03/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. YOU CANNOT USE THE AC CIRCUIT TO POWER THE SERVICE RECEPTACLE 2. DOOR ON DISCONNECT DOESN'T CLOSE 3. PLUMBERS TAPE NOT APPROVED FOR SECURING ANYTHING ESPECIALLY AN A/C UNIT 4. CANNOT CONFIRM R8 LINER WAS USED IN EXPOSED DUCT ON ROOF 5. DUCT IN ATTIC OK |
|
| 08/28/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE ANGLE IRON FRAME TO STRUCTURE 2) PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE ON ROOF 3) EXPOSED DUCT ON ROOF TO BE INSULATED WITH R8 DUCT LINER 4) NEW FLEX DUCT IN ATTIC TO BE R8 5) INSULATE T WYE IN ATTIC WITH R8 |