Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) ALL CORRECTIONS HAVE BEEN MADE |
|
| 12/15/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) SECONDARY SENSOR IS LOCATED IN PRIMARY OUTLET 2) ALL ITEMS DATED 12/01/09 HAVE BEEN CORRECTED |
|
| 12/01/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RELOCATE ELECTRIC DISCONNECT FROM BEHIND CONDENSOR 2) DO NOT USE DUCT TAPE OUTDOORS 3) DO NOT HAVE T-STAT WIRE EXPOSED OUTDOORS 4) PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET 5) USE PURPLE PRIMER PRIOR TO GLUING PVC FITTINGS 6) INSULATE SHEET METAL SLEEVE ABOVE EVAP COIL 7) PROVIDE THE REQUIRED SEDIMENT TRAP ON GAS LINE TO FURNACE 8) DO NOT USE PLASTIC WITHIN 6" OF FURNACE VENT CONNECTOR |