Permit: T09ME00544

Parcel: 123031360


Addresses:

2905 E LEE ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/12/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) ALL CORRECTIONS HAVE BEEN MADE
12/15/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) SECONDARY SENSOR IS LOCATED IN PRIMARY OUTLET
2) ALL ITEMS DATED 12/01/09 HAVE BEEN CORRECTED
12/01/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RELOCATE ELECTRIC DISCONNECT FROM BEHIND CONDENSOR
2) DO NOT USE DUCT TAPE OUTDOORS
3) DO NOT HAVE T-STAT WIRE EXPOSED OUTDOORS
4) PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET
5) USE PURPLE PRIMER PRIOR TO GLUING PVC FITTINGS
6) INSULATE SHEET METAL SLEEVE ABOVE EVAP COIL
7) PROVIDE THE REQUIRED SEDIMENT TRAP ON GAS LINE TO FURNACE
8) DO NOT USE PLASTIC WITHIN 6" OF FURNACE VENT CONNECTOR