Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T09ME00542
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SERVICE RECEPTACLE (GFCI) ON ROOF WITHIN 25' OF UNIT 2) PROVIDE 2" INSULATION (R-8) ON ALL DUCT EXPOSED TO EXTERIOR 3) CONDENSATE MUST BE PROPERLY SECURED TO BLDG 4) BREAKER IN PANEL NOT LABELED, PROVIDE BLANK OUT PLATE IN PANEL FOR MISSING BREAKER 5) CITY APPROVED LOAD CALC FOR UNIT OK |
|
| 08/27/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE HOME, PLEASE HAVE ROOF ACCESS (LADDER) PRIOR TO NEXT INSPECTION ALL PERMITS, DOCUMENTS, ETC... MUST BE AVAILABLE TO INSPECTOR AT TIME OF INSPECTION |