Permit: T09ME00540

Parcel: 117081170


Addresses:

825 S 8TH AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/04/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/01/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) ITEM 8 DATED 8/27/09 STILL NOT CORRECTED, ALL OTHER ITEMS CORRECTED
08/27/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EMT CANNOT BE USED AS BURRIAL PIPING
2) COPPER REFRIDGERATION LINES AND COPPER CONDENSATE LINES CANNOT BE IN CONTACT WITH GALVANIZED METAL
3) FLEXABLE CONDUIT TO BE STRAPPED UP OFF OFDIRT
4) PROVIDE SERVICE RECEPTACLE WITHIN 25' OF EQUIPMENT
5) PROVIDE PROPER SUPPORT UNDER UNIT (HORIZONTAL)
6) MISSING WIRE NUT AT CONDENSATE PUMP
7) CONDENSATE PUMP CANNOT HAVE PLUG CUT OFF
8) RELOCATE DISCONNECT TO A ACCESSIBLE LOCATION
9) ALL PVC PIPING TO HAVE PRIMERED JOINTS, PRIMER IS TO BE PURPLE IN COLOR