Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/01/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) ITEM 8 DATED 8/27/09 STILL NOT CORRECTED, ALL OTHER ITEMS CORRECTED |
|
| 08/27/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EMT CANNOT BE USED AS BURRIAL PIPING 2) COPPER REFRIDGERATION LINES AND COPPER CONDENSATE LINES CANNOT BE IN CONTACT WITH GALVANIZED METAL 3) FLEXABLE CONDUIT TO BE STRAPPED UP OFF OFDIRT 4) PROVIDE SERVICE RECEPTACLE WITHIN 25' OF EQUIPMENT 5) PROVIDE PROPER SUPPORT UNDER UNIT (HORIZONTAL) 6) MISSING WIRE NUT AT CONDENSATE PUMP 7) CONDENSATE PUMP CANNOT HAVE PLUG CUT OFF 8) RELOCATE DISCONNECT TO A ACCESSIBLE LOCATION 9) ALL PVC PIPING TO HAVE PRIMERED JOINTS, PRIMER IS TO BE PURPLE IN COLOR |