Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/25/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/01/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE CANNOT BE REDUCED FROM THE OUTLET SIZE OF THE UNIT 2) CLAMP GAS LINE TO WOODEN SUPPORTS 3) NEED TO TEST DUCT SMOKE DETECTORS 4) BE SURE TO HAVE AUDIBLE AND VISIBLE ALARMS 5) PROVIDE A FRESH AIR INTAKE 6) PROVIDE PERMITS AND INSPECTIONS FOR THE OTHER NEW TRANE UNITS INSTALLED WITHOUT PERMITS. LOOK FOR THE SAME CODE VIOLATIONS |