Permit: T09ME00529

Parcel: 128100810


Addresses:

5410 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T09ME00529

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/25/2009 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
09/01/2009 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSATE CANNOT BE REDUCED FROM THE OUTLET SIZE OF THE UNIT
2) CLAMP GAS LINE TO WOODEN SUPPORTS
3) NEED TO TEST DUCT SMOKE DETECTORS
4) BE SURE TO HAVE AUDIBLE AND VISIBLE ALARMS
5) PROVIDE A FRESH AIR INTAKE
6) PROVIDE PERMITS AND INSPECTIONS FOR THE OTHER NEW TRANE UNITS INSTALLED WITHOUT PERMITS. LOOK FOR THE SAME CODE VIOLATIONS