Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09ME00523
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/25/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 09/01/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TERMINATE CONDENSATE TO THE GROUND 2) SUPPORT COPPER TUBE EVERY 6' 3) PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE ON ROOF WITH A OUTDOOR BOX AND COVER 4) PROVIDE ON OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET ON COIL 5) PROVIDE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 6) TIGHTEN LOOSE ROMEX CONNECTORS ONTO POWER CORDS |
|
| 08/31/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
| 08/28/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE SCHEDULE YOUR INSPECTION WHEN SOMEONE WILL BE HOME |
|
| 08/27/2009 | MECHANICAL - FINAL | Cancelled | CANCELLED PER CONTRACTOR GABE GARCIA #971-1951 | |
| 08/27/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |