Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 08/21/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT GAS LINE 2) RELOCATE SHUT OFF VALVE TO ONE UNIT 3) PROVIDE FRESH AIR INTAKE 4) TERMINATE CONDENSATE DRAINS TO AN APPROVED LOCATION 5) REPLACE LOW VOLTAGE WIRING ON ROOF-USE CONDUIT 6) SUPPORT ELECTRIC CONDUITS 7) SUPPORT PVC EVERY 4' AND PAINT WITH LATEX PAINT 8) PROVIDE REDWOOD OR PRESSURE TREATED SLEEPERS UNDER A/C UNITS SPANNING MIN 3 JOISTS 9) REPAIR BROKEN ELECTRIC CONNECTION TO A/C 2 DISCONNECT 10) PORTIONS OF CANVAS CONNECTORS EXPOSED TO SUN |