Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09ME00510

Parcel: 12108005A


Addresses:

6225 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09ME00510

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/25/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
08/21/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT GAS LINE
2) RELOCATE SHUT OFF VALVE TO ONE UNIT
3) PROVIDE FRESH AIR INTAKE
4) TERMINATE CONDENSATE DRAINS TO AN APPROVED LOCATION
5) REPLACE LOW VOLTAGE WIRING ON ROOF-USE CONDUIT
6) SUPPORT ELECTRIC CONDUITS
7) SUPPORT PVC EVERY 4' AND PAINT WITH LATEX PAINT
8) PROVIDE REDWOOD OR PRESSURE TREATED SLEEPERS UNDER A/C UNITS SPANNING MIN 3 JOISTS
9) REPAIR BROKEN ELECTRIC CONNECTION TO A/C 2 DISCONNECT
10) PORTIONS OF CANVAS CONNECTORS EXPOSED TO SUN