Permit: T09ME00506

Parcel: 141201590

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/30/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
11/16/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PROPER CLEARANCE TO COMBUSTIBLES (CORK TAPE) FROM FLUE PIPE
2) ITEM 3 DATED 10/27/10 NOT CORRECTED. NEXT FAILED INSPECTION WILL RESULT IN A REFEE
10/27/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE A ROMEX CONNECTOR FOR POWER CARD FOR FURNACE
2) FURNACE VENT CONNECTOR MUST HAVE MINIMUM 1/4" PER FT. SLOPE
3) IMPROPER WIRING METHODS AT SURGE PROTECTOR