Permit: T09ME00502

Parcel: 132162020


Addresses:

4701 S CALLE MIURA

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/02/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/21/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSULATION TURN AWAY AND FALLING DOWN WHERE NEW DUCT IS TIED INTO EXISTING DUCT
2) ITEMS 2,3 & 8 DATED 10/02/09 STILL NOT CORRECTED
10/02/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL EXTERIOR DUCT IS TO BE MIN. R-8 (2") DUCT ON ROOF IS ONLY 4.2 REMOVE AND REPLACE
2) PROVIDE CITY APPROVED LOAD CALC. FOR NEW UNIT ON ROOF
3) PROVIDE GAS PRESSURE TEST PERMIT
4) ALL PVC EXPOSED TO EXTERIOR TO BE SEALED WITH LATEX PAINTOR EQUAL
5) ALL PVC PIPE TO HAVE ALL JOINTS PRIMED, ALL PRIMER IS TO BE PURPLE IN COLOR
6) ALL PVC IS TO BE BLOCKED UP OFF OF ROOF MIN. 1.5
7) PROVIDE BLANK OFF PLUG IN DISCONNECT BOX
8) PROVIDE METAL DEVICE TO BULL NOSE EDGE OF ALL DUCT LINER WITHIN AIR SYSTEM
9) TERMINATE CONDENSATE AT AN APPROVED LOCATION
10) PROVIDE SERVICE RECEPT ON ROOF (GFI)
11) ELECTRIC ROOF JACK LEAKING, SEAL TITE NOT PROPERLY STRAPPED TO STRUCTURE