Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09ME00499
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 08/19/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) DO NOT CONNECT TWO CONDUCTORS TO 1 LUG IN DISCONNECT 2) USE WIRE CONNECTORS IF NECESSARY 3) DO NOT USE DUCT TAPE OUTDOORS ON LINE SET 4) USE OUTDOOR TAPE OR UV RATED ZIP TIES 5) ALL GLUED PVC FITTINGS MUST HAVE PURPLE PRIMER PRIOR TO GLUE |