Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09ME00498
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/09/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
09/09/2009 | MECHANICAL - FINAL | Approved | ||
09/01/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SECONDARY DRAIN ON COILS 2) ALL PVC IS TO HAVE PRIMER AT ALL JOINTS, PRIMER IS TO BE PURPLE IN COLOR 3) SEAL ALL NEW DUCT JOINTS AND ? DUCT CONNECTS TO COIL 4) REPAIR INSULATION ON REFRIDGERATION PIPING AS NEEDED TO RESIST SWEATING 5) GUEST HOUSE C.U. IS OVER FUSED 6) PROVIDE SERVICE RECEPTACLE WITHIN 25' OF SERVICEABLE EQUIPMENT 7) FLUE VENTING NOT TO EXCEED 60 DEGREE 8) CONDENSATE PIPING AT GARAGE UNIT APPEARS TO BE RUNNING UP HILL 9) PROVIDE SEDIMENTS TRAPS ON GAS PIPING TO EQUIPMENT 10) PROVIDE NEW GAS FLEX'S ON ALL NEW EQUIPMENT INCLUDING W/H |