Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09ME00485
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/09/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* VENT ON CONDENSATE DRAIN MUST BE DOWNSTREAM OF THE TRAP. A VENT IS NOT RE? SECURE ELEC CONDUCTS IN CLOSET. PLASTIC CONDESATE PUMP NOT ALLOWED IN A RETURN ?. PROVIDE HOSE CLAMPS OR PLASTIC HOSE. MARK UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED. EXTEND 3/8 COPPER DRAIN TO WITHIN 6" OF GROUND WITH AN 90 BEND AT BOTTOM. SECURE TO STRUCTURE TO BLOCKS ON ROOF |