Permit: T09ME00476

Parcel: 11502095G


Addresses:

308 E LINDEN ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/15/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/26/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
308:
1) PROVIDE COVER PLATE ON RECEPT
2) PROVIDE SECONDARY DRAIN
3) ALL PVC JOINTS TO HAVE PRIMER, PAINTING EXTERIOR OF PIPE WITH PRIMER NOT ACCEPTABLE
310:
1) ITEMS DATED 8/20/09 #5 & 6, ALL OTHER ITEMS NEED TO BE CORRECTED
08/20/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1)ALL PVC PIPE TO HAVE PRIMOR PURPLE IN COLOR
2)PROVIDE SECONDARY DRAIN ON COIL
3)PROVIDE INSULATION SHIELD AROUND B-VENT
4)PROVIDE PROPER ELECTRICAL CONNECTIORS
5)REMOVE WOOD DUCTING AND REPLACE WITH SHEET METAL OR OTHER APPROVED MATERIAL
6)PROVIDE DISCONNECT DEVICE AT F.A.U.
7)PROVIDE PROPER WIRING AT C.U. UNITS
8)THESE NOTES APPLY TO BOTH UNITS 308 & 310
08/19/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DOG IN YARD AND UNABLE TO GAIN ACCESS