Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09ME00461
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 03/19/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CAP OFF VENT UPSTREAM OF CONDENSATE TRAP 2) GAS FLEX APPEARS TO BE LONGER THAN 3' IN LENGTH 3) COULD NOT GET INTO ATTIC TO MEASURE FOR PROPER LENGTH |
|
| 10/20/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DO NOT USE SINGLE WALL VENT PIPE IN THE ATTIC 2) REMOVE ALL FOIL TAPE 3) VENT ON CONDENSATE TRAP TO BE DOWNSTREAM OF TRAP 4) GAS FLEX NOT TO EXCEED 3' IN LENGTH 5) PROVIDE A 90 DEGREE ELBOW AT BOTTOM OF CONDENSATE TERMINATION 6) NEED ACCESS TO CIRCUIT BREAKER |
|
| 10/01/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE SCHEDULE YOUR INSPECTION WHEN SOMEONE WILL BE HOME |