Permit: T09ME00448

Parcel: 12501052A


Addresses:

2641 E 10TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/27/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/25/2009 MECHANICAL - FINAL Denied 1) GAS PRESSURE TEST OK
2) PROVIDE PRIMER ON ALL PVC JOINTS
3) ALL PVC PIPE EXPOSED TO EXTERIOR IS TO BE PAINTED WITH LATEX PAINT
4) PROVIDE ROOF JACKS ON ALL ROOF PENETRATIONS
5) PROVIDE PROPER DESCRIPTION OF WORK, THIS IS A NEW INSTALL, EXISTING SYSTEM WAS A SPLIT SYSTEM
6) PROVIDE CITY APPROVED LOAD CALC FOR NEW UNIT ON ROOF
7) ELECTRICAL WIRING ON ROOF NOT PROPERLY INSTALLED
8) ALL DUCTING IN VENTED ATTIC TO BE MIN R-8 PER I.E.C.C. 2006
08/24/2009 MECHANICAL - FINAL Denied GAS PRESSURE TEST FAILED