Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/02/2009 | MECHANICAL - INTERMEDIATE | Approved | ||
| 07/31/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PROPER DESCRIPTION OF WORK (NEW INSTALL) 2) PROVIDE PERMIT FOR ELECTRICAL UPGRADE 3) PROVIDE CITY APPROVED LOAD CALCULATIONS ON ROOF 4) ALL PVC JOINTS TO BE PRIMED (PRIMER IS TO BE PURPLE IN COLOR PER UPC) 5) PVC SUPPORT NOT TO EXCEED 48" 6) PVC PIPING EXPOSED TO WEATHER IS TO BE PAINTED WITH LATEX PAINT 7) VERIFY DUCT IS INSULATED ABOVE CEILING 8) PROVIDE GFI SERVICE RECEPTACLE ON ROOF 9) COMPLETE ELECTRICAL INSTALLATION ON ROOF |