Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/11/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 07/29/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE A SEDIMENT TRAP AT GAS LINE TO FURNACE 2) PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE AT THE CONDENSOR 3) 50 AMP BREAKER FOR CONDENSOR IS TO LARGE, 35 AMP IS MAX |