Permit: T09ME00346

Parcel: 140241570


Addresses:

1310 E GINTER RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/29/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/10/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT ALL FLEX DUCTS EVERY 5' AND OFF THE EARTH MINIMUM
2) 4" INSULATE ALL SHEET METAL FITTINGS
3) USE ONLY UL181 LISTED TAPE AND MASTIC
4) 25 PSI TEST IS OK