Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/02/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/24/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE A SECONDARY OVERFLOW SENSOR ON EVAP. COIL 2. NO PLASTIC WITHIN 6" OF VENT CONNECTOR 3. PROVIDE A SEDIMENT TRAP AT GAS LINE CONNECTION TO FURNACE 4. CONNECT OVERFLOW SENSOR ON CONDENSATE PUMP 5. GLUE ALL FITTINGS ON CONDENSATE DRAIN 6. EXISTING DUCT HAS NO INSULATION - THIS COULD BECOME A PROBLEM W/CONDENSATION AND POOR EFFICIENCY ALL AIR CONDITIONING DUCT MUST BE INSULATED AND MUST HAVE A VAPOR BARRIER. |