Permit: T09ME00324

Parcel: 133261890


Addresses:

8141 E 3RD ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/02/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/24/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE A SECONDARY OVERFLOW SENSOR ON EVAP. COIL
2. NO PLASTIC WITHIN 6" OF VENT CONNECTOR
3. PROVIDE A SEDIMENT TRAP AT GAS LINE CONNECTION
TO FURNACE
4. CONNECT OVERFLOW SENSOR ON CONDENSATE PUMP
5. GLUE ALL FITTINGS ON CONDENSATE DRAIN
6. EXISTING DUCT HAS NO INSULATION - THIS COULD BECOME A PROBLEM W/CONDENSATION AND POOR EFFICIENCY
ALL AIR CONDITIONING DUCT MUST BE INSULATED AND MUST HAVE A VAPOR BARRIER.