Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE RECEPTACLE NOT PROPERLY WIRED. YOU CANNOT PIGGY BACK OFF OF A 70 AMP CIRCUIT, YOU MUST PROVIDE A SEPERATE FEDD WITH A NEUTRAL 2) FUSE BLOCK FOR A/C UNIT IS BROKEN, THE SCREWS THAT HOLD THE FUSE RETAINING CLIPS IN ARE STRIPPED OUT. REPLACE BLOCK OR DISCONNECT BOX |
|
| 06/15/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE SERVICE RECEPTACLE WITH GFCI WITHIN 25' OF UNIT 2. PROVIDE OUTSIDE AIR HOOD AND BALANCE PER I.M.C 3. CONDENSATE CANNOT TERMINATE IN WASTE VENT, IT MUST BE IN AN APPROVED LOCATION 4. ONLY PRESSURE TREATED OR REDWOOD ALLOWED TO BE EXPOSED 5. UNIT DATA PLATE NOT IDENTIFIED |