Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/22/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* OK TO ENCLOSE FAN COILS AND INSTALL GRILLS |
|
| 06/19/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/17/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO COMBUSTIBLE MATERIAL ALLOWED IN PLENUM 2. H/W & C/W NOT PROPERLY INSTALLED 3. PVC IS CONSIDERED COMBUSTIBLE MATERIAL (CPVC IS ALLOWABLE) 4. PROVIDE DISCONNECT FOR SERVICING WITHIN VIEW OF AIR HANDLER 5. PROVIDE ADEQUATE RETURN AIR OPENING 6. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR RETURN SIZING |