Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09ME00246

Parcel: 11307147A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09ME00246

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/06/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/22/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
OK TO ENCLOSE FAN COILS AND INSTALL GRILLS
06/19/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
06/17/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NO COMBUSTIBLE MATERIAL ALLOWED IN PLENUM
2. H/W & C/W NOT PROPERLY INSTALLED
3. PVC IS CONSIDERED COMBUSTIBLE MATERIAL (CPVC IS ALLOWABLE)
4. PROVIDE DISCONNECT FOR SERVICING WITHIN VIEW OF AIR HANDLER
5. PROVIDE ADEQUATE RETURN AIR OPENING
6. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR RETURN SIZING