Permit: T09ME00240

Parcel: 112073800


Addresses:

3010 E COPPER ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/06/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/16/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE RECEPTACLE HAS AN OPEN GROUND (NOT PROPERLY WIRED)
2. DISCONNECT STILL NOT INSTALLED AT MINI-SPLIT
3. ALL OTHER CORRECTIONS MADE - DATED 6/3/09
06/12/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RANG BELL & KNOCKED AT 11:30
NO ONE PRESENT
RECALL
06/03/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPLACE THE SCREEN THAT WAS REMOVED FROM THE HIGH COMBUSTION AIR OPENING
2) MINI SPLIT CONDENSOR IS OVER FUSED. SECURE MINI CONDENSOR TO SLEEPERS ON ROOF
3) PROVIDE A BUSING IN ELECTRIC DISCONNECT FOR LARGE CONDENSOR
4) PROVIDE A NEW CIRCUIT FOR THE SERVICE RECEPTACLE. YOU CANNOT USE THE A/C CIRCUIT FOR THIS. YOU MUST HAVE A NEUTRAL WIRE. YOU CANNOT HAVE 2 WIRES ATTACHED TO 1 LUG IN A DISCONNECT. YOU CANNOT USE A GROUND AS A REPLACEMENT FOR NEUTRAL. YOU MIGHT BE ABLE TO USE THE OLD EVAP COOLER CIRCUIT
5) PROVIDE A DISCONNECT AT MINI FAN COIL
6) TERMINATE MINI FAN CONDENSATE INTO PVC WITH A PROPER FITTING