Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09ME00240
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/06/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
06/16/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE RECEPTACLE HAS AN OPEN GROUND (NOT PROPERLY WIRED) 2. DISCONNECT STILL NOT INSTALLED AT MINI-SPLIT 3. ALL OTHER CORRECTIONS MADE - DATED 6/3/09 |
|
06/12/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* RANG BELL & KNOCKED AT 11:30 NO ONE PRESENT RECALL |
|
06/03/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REPLACE THE SCREEN THAT WAS REMOVED FROM THE HIGH COMBUSTION AIR OPENING 2) MINI SPLIT CONDENSOR IS OVER FUSED. SECURE MINI CONDENSOR TO SLEEPERS ON ROOF 3) PROVIDE A BUSING IN ELECTRIC DISCONNECT FOR LARGE CONDENSOR 4) PROVIDE A NEW CIRCUIT FOR THE SERVICE RECEPTACLE. YOU CANNOT USE THE A/C CIRCUIT FOR THIS. YOU MUST HAVE A NEUTRAL WIRE. YOU CANNOT HAVE 2 WIRES ATTACHED TO 1 LUG IN A DISCONNECT. YOU CANNOT USE A GROUND AS A REPLACEMENT FOR NEUTRAL. YOU MIGHT BE ABLE TO USE THE OLD EVAP COOLER CIRCUIT 5) PROVIDE A DISCONNECT AT MINI FAN COIL 6) TERMINATE MINI FAN CONDENSATE INTO PVC WITH A PROPER FITTING |