Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/18/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE DBL WALL THRU OUT COVER FOAM BOARD WITH S. METAL 2) PROVIDE 1" CLEARANCE TO COMBUSTIBLES ON ? WALL INSTALLATIONS |
|
| 07/23/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO SINGLE WALL PIPE ALLOWED IN ATTIC SPACE, EXTEND 6" BELOW CEILING 2) PIPE INSTALLED UPSIDE DOWN |
|
| 07/22/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1 CALLED PHONE NUMBER UNDER APPLICANT, WRONG NUMBER, MESSAGE REQUESTED A PHONE CALL TO ALLOW TIME TO MEET AT LOCATION, SINCE UNABLE TO MAKE CONTACT, I DID NOT SHOW UP AT ADDRESS ABOVE |
|
| 06/24/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DO NOT TERMINATE DOUBLE WALL VENT PIPE INTO SINGLE WALL - EXTEND FURNACE VENT 3' ABOVE EVAP. COOLER USE 4" SINGLE WALL FROM FURNACE TO VENT AT CEILING DO NOT SEAL WITH TAPE. |