Permit: T09ME00191

Parcel: 10603170E

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/02/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
06/30/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) FINAL IN CONDENSATE DRAIN NOT GLUED
2) WATER RUNNING INTO ROOF
3) RESCHEDULE FOR FINAL
06/22/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE MIN. R8 DUCT LINER IN EXPOSED DUCT ON ROOF
2. PROVIDE A FRESH AIR INTAKE
3. BALANCE SYSTEM AS PER QUANTITIES ON PLANS
4. PROVIDE BALANCE REPORT
5. SUPPORT ELEC. CONDUIT AS PER N.E.C
6. LOW VOLTAGE WIRING MUST BE PROTECTED
7. USE CONDUIT
8. EXTEND CONDENSATE DRAIN TO THE SCUPPER
9. BLOCK & CLAMP EVERY 4' AND PAINT W/LATEX PAINT
10. SECURE THE ELEC. DISCONNECT
11. PROPERLY CONNECT STRANDED WIRE TO LUG IN DISCONNECT