Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T09ME00182
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE GUARD RAIL ON ALL SERVICEABLE EQUIPMENT WITHIN 10' OF ROOF EDGE 2. PROVIDE OUTSIDE AIR AT RETURN DUCT AND BALANCE PER I.E.C.C. AND/OR I.M.C 3. IDENTIFY UNIT DATA PLATE FOR ELEC. HEAT IF ANY OR NONE 4. PROVIDE G.F.C.I AT ROOFTOP SERVICE 5. WHEN O.S.A IS INSTALLED MAKE SURE WASTE VENT IS NOT WITHIN 10' |