Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/13/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE PIPING NOT PROPERLY SUPPORTED 2) CONDENSATE PIPING NOT PROPERLY COATED 3) CONDUIT NOT PROPERLY SUPPORTED 4) PROVIDE MEANS OF ADJUSTING OUTSIDE AIR 5) PROVIDE OUTSIDE AIR CALCULATIONS AND REPORT PER I.E.C.C. AND I.M.C. 6) NEUTRAL WIRE CANNOT BE USED AS LINE VOLTAGE WIRING (HOT) 7) PROVIDE OUTSIDE AIR FILTER 8) PROVIDE A MIN. R-8 INSULATION ON ALL EXTERIOR DUCT |