Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE THE REQUIRED DRAWING APPROVED BY CITY OF TUCSON ALLOWING AN A/C UNIT ON THE ROOF. 2. PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE ON THE ROOF 3. PROVIDE MIN. 1/8" PER FT. SLOPE ON CONDENSATE DRAIN AND PAINT WITH LATEX PAINT 4. PROVIDE ROOF JACKS AT ELEC & CONDENSATE PENETRATIONS THRU THE ROOF 5. IDENTIFY THE CIRCUIT BREAKER FOR AC UNIT 6. OK TO SHEETROCK HALLWAY CEILING |