Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09ME00106
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/22/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
08/21/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/04/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) ITEMS 1,2,3,4,7,8 & 9 DATED 4/14/09 HAVE BEEN CORRECTED 2) DUCT SMOKE DETECTOR INSTALLED IS NOT APPROVED FOR EXTERIOR INSTALLATION |
|
07/23/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONTRACTOR NOT ON SITE, NO ROOF ACCESS |
|
04/15/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/14/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TERMINATE CONDENSATE AT APPROVED LOCATION 2) PVC BLOCKING NOT TO EXCEED 48" 3) PROVIDE OUTSIDE AIR HOOD 4) BALANCE OUTSIDE AIR PER I.M.C. 5) PROVIDE DUCT SMOKE DETECTOR ON EQUIPMENT WITH C.F.M. IN EXCESS OF 2000 6) PROVIDE AUDIO AND VISIBLE ALARM AT CONTINOUSLY MONITORED LOCATION FOR DUCT SMOKE DETECTOR 7) GAS PIPING SIZE CANNOT BE SMALLER IN DIAMETER THAN UNIT INLET 8) PROVIDE SEDIMENT TRAP AT GAS PIPING 9) PROVIDE A MINIMUM OF R-8 ON ALL DUCT EXPOSED TO EXTERIOR |