Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/04/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE SCREEN IN T-TAPS ON ROOF INSTALL KITCHEN HOODS AND GRILLES |
|
| 03/23/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/20/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO COMBUSTIBLE MATERIALS ALLOWED IN RETURN PLENUM 2. ALL PVC PIPING MUST USE PRIMER (PURPLE IN COLOR) PRIOR TO GLUE 3. PVC NOT ALLOWED IN RETURN PLENUM AS IT IS CONSIDERED A NON-PLENUM RATED MATERIAL 4. RTU's NOT INSPECTED |