Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/28/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) INSPECTION DOES NOT INCLUDE DUCT WORK SYSTEM 2) INSPECTION ONLY FOR ROOF TOP UNIT ONLY 3) DESCRIPTION ON PERMIT READS HVAC SYSTEM |
|
| 05/27/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DOES NOT INCLUDE ANY NEW DUCT WORK IN ATTIC 2) PROVIDE A STAMPED APPROVED CITY OF TUCSON MECHANICAL SYSTEM UPGRADE 3) PROVIDE GAS BOND 4) DRIP LEG WATER HEATER 5) PROVIDE PRESSURE TEST FOR NEW GAS LINE 6) PROVIDE ACCESS TO UNIT AND ROOF TOP 7) NOTES 3, 4, 5 & 6 FROM PREVIOUS |
|
| 05/20/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COLOR CODE HOT WIRE 2) PAINT CONDENSATE LINE 3) ALL NEW DUCT WORK INSTALLED, PROVIDE PROOF OF PERMIT AND APPROVALS 4) PROVIDE DRAWING FOR STRUCTUAL REQUIREMENTS FOR ROOF TOP UNIT ON 2 X 6 CONVENTIONAL RAFTERS TO INCLUDE GAS LINE 5) PROVIDE GAS PRESSURE TEST 6) TOTAL REMODEL EXTERIOR AND INTERIOR 7) REFER TO DNR |
|
| 05/14/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PAPERWORK FOUND 2) PROVIDE ACCESS TO ROOF TOP UNIT 3) PROVIDE ACCESS TO HOUSE |
|
| 03/30/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) HOUSE IS LOCKED 2) 69,000 BTU ROOF UNIT, WHAT SIZE GAS LINE REQUIRED CAN'T FIND MAIN GAS LINE INTO HOUSE NUMEROUS GAS LINES CUT OFF AROUND EXTERIOR 3) COLOR CODE HOT WIRES FOR ROOF UNIT |