Case: T09FR03857

Parcel: 130130670


Addresses:

3601 E 34TH ST 2M


Inspection Status: Approved

Inspection History: VIOL - HAZARDOUS MATERIALS,GEN

Case Number - T09FR03857

Inspection Description - VIOL - HAZARDOUS MATERIALS,GEN

Inspection Status - Approved

Date Description Inspector Results Comments
01/06/2010 VIOL - HAZARDOUS MATERIALS,GEN Approved ok
12/23/2009 VIOL - HAZARDOUS MATERIALS,GEN Violation VIOALTION OF TFC 2006 EDITION (TABLE 2703.1.1 (1) STATES THAT ANY ACCUPANCY WITH STORAGE OF MORE THAN 30 GALLONS OF A CLASS 1A FLAMMABLE LIQUID IS CLASSIFIED AS AN H2 OCCUPANCY. ANY OCCUPANCY THAT HAS AN OPEN-USE SYSTEM OF MORE TAN 10 GALLONS OF A CLASS 1A FLAMMABLE LIQUID IS CLASSIFIED AS AN H2 OCCUPANCY.

TFC 3404.4.3 - STORAGE AREAS SHALL BE PROVIDED WITH SECONDARY CONTAINMENT.

TFC 3404.4.2 - OUTDOOR STARAGE MUST BE KEPT 50 FEET FROM LOT LINES AND 10 FT FROM A PUBLIC WAY.

YOU ARE HEREBY ORDERED TO REMOVE THE 55 GAL DRUM OF ISOPROPYL ALCOHOL FROM THE INSIDE OF YOUR BUILDING. iT CURRENTLY DOES NOT MEET THE SAFETY REQUIREMENTS OF AN H2 OCCUPANCY. ANY VOLUME OF FLAMMABLE LIQUIDS STORED INSIDE IN A QUANTITY GREATER THAN 30 GALLONS OF CLASS 1A FLAMMABLE WILL CAUSE Y;OU TO EXCEED YOUR MAXIMUM ALLOWABLE QUANTITIES.
FURTHER ANY STORAGE AREA OUTDOORS MUST BE PROVIDED WITH SECONDARY CONTAINMENT AND BE KEPT 50 FEET FROM LOT LINES AND 10 FEET FROM A PUBLIC WAY.

THE DRUM WILL BE MOVED OUT OF THE BUILDING BY THE CLOSE OF BUSINESS TOMORROW 12/23/09. THE INSPECTOR ASSIGNED TO YOUR AREA WILL CONTACT YOU FOR FOLLOW REGARDING YOUR PROCESSES AND OCCUPANCY CLASSIFICATION.