Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T09FR03847
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/2010 | INSP - FULL | Approved | approved | |
12/22/2009 | INSP - FULL | Correction Required | _____ 3003.5 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. Required Action: Secure compressed gas cylider _____ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Required Action: Relpace missing ceiling tile _____ 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Required Action: NE Exit sign shallbe illuminated _____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied -Provide back up power supply for all required exit illumination Required Action: Emergency back up ilghtinmg shall operate: -2 each in pharmacy -1 above the picture frames area _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. Required Action: Remove the extension cord going through the ceiling on the sales floor _____ 2703.5.1 Markings. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. Rooms or cabinets containing compressed gases shall be conspicuously labeled: Required Action: All cnotainers inte "photo" area shall be prperly labeled 110.1 General. If during the inspection of a premises, a building or structure or any building system, in whole or in part, constitutes a clear and inimical threat to human life, safety or health, the fire code official shall issue such notice or orders to remove or remedy the conditions as shall be deemed necessary in accordance with this section and shall refer the building to the building department for any repairs, alterations, remodeling, removing or demolition required. Required Action: Clean up the area around the "photo shop." Curretly there is evidence of chmical spilled on the floor and surrounding area. _____ 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. Required Action: Remove the stock which blocks teh exiting stairway from the loft area. |