Case: T09FR03840

Parcel: 133231400


Addresses:

7805 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR03840

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
08/13/2010 VIOL - MEANS OF EGRESS Approved
12/21/2009 VIOL - MEANS OF EGRESS Violation Panic hardware hard to open:
1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following:
1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width.
2. A maximum unlatching force of 15 pounds (67 N).
______ Fix hardware so opens easily.
12/21/2009 VIOL - MEANS OF EGRESS Violation Emergency lighting:

IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located]

______Fix all inoperative emergency lights.
12/21/2009 VIOL - MEANS OF EGRESS Violation Door needs pull handle:
TFC 1003.6 Means of egress continuity.
______Place a pull handle on the door by the rest room.