Case: T09FR03840

Parcel: 133231400


Addresses:

7805 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR03840

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
08/13/2010 VIOL - FIRE PROTECTION SYSTEMS Approved
12/21/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishers not tagged / inspected:

TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
12/21/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Sign missing from pull station:
TFC2006/ 904.11.4 Special provisions for automatic sprinkler systems.
Automatic sprinkler systems protecting commercial- type cooking equipment shall be supplied from a
separate, readily accessible, indicating-type control valve that is identified.

______ Have pull station clearly marked.
12/21/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Maintain sprinkler system: 2 items:
901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

______All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code.

______ Adjust and tighten heads covering char broiler - to be done by service company and documentation given to Fire Marshal.