Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T09FR03761

Parcel: 12110001C


Addresses:

4725 E PIMA ST


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR03761

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2010 VIOL - BUILDING SVCS & SYSTEMS Approved A Surge Protector is now in use. In FULL COMPLIANCE!
12/14/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required 1. An unfused extension cord is used to power the computers in Classrooms # 17 & 18. Remove the extension cords. INTERNATIONAL FIRE CODE (IFC) 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.