Case: T09FR03716

Parcel: 136027250


Addresses:

1281 S STOCKER DR


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR03716

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
12/28/2009 INSP - FULL Approved abated
12/10/2009 INSP - FULL Correction Required Dynamic Emission Repair
ATTN: Julio Lopez
1281 S. Stocker
Tucson, AZ. 85710

Dear Mr.Lopez

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on December 10, 2009. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications). A Re-inspection will be performed on or about December 28, 2009.

Notice of Violations:
1. _____ 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property:
Pima County Addressing Code:
>50 feet from the road: 15 inches
<50 feet from the road: 12 inches
Individual units: 3 inches

Required Action: Provide address meeting the Pima County Addressing Code of 12 inches in height

2. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

Required Action: Remove the extension cord near front desk

3. _____ 2703.5.1 Markings. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. Rooms or cabinets containing compressed gases shall be conspicuously labeled:

Required Action: Label all 55 gallon drums to communicate their contents

4. _____ 901.6/ 901.7 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

Required Action: All fire extinguisher shall be serviced annually and properly mounted. (Currently the extinguishers are tagged 1995)

5. _____ 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited

Required Action:
- Cover opening in the electrical panel.
- Replace the cover-plate near the front desk

6. _____ 605.4 Multiplug adapters. Multiplug adaptors, such as cube adaptors, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

Required Action: Remove multi-cube adapter near front desk

7. _____ 110.1.1 Unsafe conditions. Structures or existing equipment that are or hereafter become unsafe or deficient because of inadequate means of egress or which constitute a
fire hazard, or are otherwise dangerous to human life or the public welfare, …. shall be deemed an unsafe condition

Required Action: The stairs from the loft have been removed to install the lift. As a result a fall hazard has been created. Provide an adequate means to protect the opening to prevent falling.

The Tucson Fire Department is committed to the protection of your property. Your help as a business owner and as a citizen is greatly appreciated.