Inspection History Details
Inspection Status: Continued
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T09FR03685
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Continued
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/2010 | VIOL - FIRE PROTECTION SYSTEMS | Continued | The sprinkler was installed in the mens locker room. Waiting for the T.M. Workshop to have the sprinklers installed. |
|
12/02/2009 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | The mens locker room and Traffic Maintenance do not have adequate sprinkler coverage. Install additional sprinklers to provide the proper coverage. IFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. |