Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T09FR03675
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2010 | VIOL - FIRE PROTECTION SYSTEMS | Approved | UPON REINSPECTION HOOD SYSTEM WAS SERVICED AND ANSUL BOTTLES HAVE BEEN HYDRO TESTED. NO DEFICIENCIES ON REPORT. GOOD JOB. | |
| 12/02/2009 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | IFC 904.8.2 High-pressure cylinders. High-pressure cylinders shall be weighed and the date of the last hydrostatic test shall be verified at 6-month intervals. Where a container shows a loss in original content of more than 10 percent, the cylinder shall be refilled or replaced. ___1. BOTTLES DUE FOR HYDRO TEST WITHIN THE COMMERCIAL COOKING HOOD SYSTEM. Re-inspection date scheduled on or after December 8th, 2009. If you have any questions or concerns please call Inspector Motto at 8377127. Thank you, _____________________________________________ William Motto, Inspector, Tucson Fire Department __________________________ - I have received a copy of this inspection report. Building Representative Re-inspection approved: ___________________________Date:__________ Captain - Tucson Fire Dept. ________________________________________ |