Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T09FR03647
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/24/2009 | VIOL - MEANS OF EGRESS | Correction Required | 1. The EXIT light in the Music Room is not illuminated. Illuminate the unit. IFC 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. 2. The 2 EXIT doors leading from the cafeteria do not have illuninated EXIT sigms signifying them as EXITS. Install EXIT lighting units above the doorways. IFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. |