Case: T09FR03621

Parcel: 116150790

Inspection Status: Approved

Inspection History: INSP - SELF INSPECTION PROGRAM

Date Description Inspector Results Comments
12/09/2009 INSP - SELF INSPECTION PROGRAM Approved All violations have been corrected.
11/24/2009 INSP - SELF INSPECTION PROGRAM Scheduled RI on 11/20/09
11/24/2009 INSP - SELF INSPECTION PROGRAM Violation 1. TFC 1011.4 Exit signs shall be illuminated at all times.
Correction: You will cause your exit signs to light.

2. TFC 703.1 The required fire-resistance-rating of fire-resistance-rated construction will be maintained.
Correction: Repair or replace damabed and missing ceiling tiles in :
A) mens room
B) Paul's office

3. TFC 605.4 Relocatable powertaps shall have overcurrent protection.
Correction: Replace adapter cord (connected to TV in the waiting room) with a powerstrip that has oversurge protection.

4. TFC 605.6 Approved covers shall be provided for all switch and electrical outlet boxes.
Correction: You will place an approved cover on your outside outlet box on the SE exterior corner of your building.