Case: T09FR03619

Parcel: 11612067B


Addresses:

1202 W NIAGARA ST

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
11/20/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

_____1. Service and tag all portable fire extinguishers.

_____2. Service and tag the kitchen hood extinguishing system.
11/20/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.

_____1. Clean and remove all grease accumulation from the kitchen hood system.