Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T09FR03616

Parcel: 11720007A


Addresses:

255 W ALAMEDA ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
12/07/2009 INSP - FULL Approved SUPPLIES REMOVED TO BELOW 18 INCHES. CLOSED!
11/19/2009 INSP - FULL Correction Required Supplies stacked on top of a partition wall inside RM 12 blocking the spray pattern of the sprinkler. Rmove the obstructions. INTERNATIONAL FIRE CODE 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.