Case: T09FR03605

Parcel: 141177400


Addresses:

7335 S HOUGHTON RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR03605

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
12/02/2009 INSP - FULL Approved All discrepencies corrected
11/18/2009 INSP - FULL Correction Required FIRE INSPECTION REPORT

11-16-09
Gas City
7335 S. Houghton
Tucson, AZ


Dear Sir or Madam,

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on 11-17-2009. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code with modifications. A Re-inspection will be performed on or about December 2nd 2009.


605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring.

" Remove the extension cords on the ice cream machine

901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

" Fire extinguishers shall be inspected annually

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.







1028.8 Panic Hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.






Re-Inspected by __________________ Approved Disapproved


Sincerely,



Conrad Funke
Fire Inspector
Tucson Fire Department
797 E. Ajo
Tucson, AZ 85713-5011
(520) 791-4502 Ext. 102