Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - HAZARDOUS MATERIALS,GEN
Case Number - T09FR03579
Inspection Description - VIOL - HAZARDOUS MATERIALS,GEN
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2009 | VIOL - HAZARDOUS MATERIALS,GEN | Approved | RE-inspection on 12/22/09. All violations abated. | |
| 11/17/2009 | VIOL - HAZARDOUS MATERIALS,GEN | Violation | ____Maximum allowable quantity of race fuel exceeded in storage. 2006 IFC TABLE 2703.1.1 MAXIMUM ALLOWABLE QUANTITY. For race fuels, (Class IA) Maximum allowable quantity is 60 Gallons in a control area. currently ther is over 120 stored in the rear room. Move fuel in excess of 60 Gallons to another control (storage) area/room to remain under the maximum allowable quantity. |