Case: T09FR03578

Parcel: 133170680

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR03578

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2009 VIOL - MEANS OF EGRESS Approved All abated
11/17/2009 VIOL - MEANS OF EGRESS Violation Double keyed lock on door:
1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

______ Remove Keyed dead bolt. [2 office doors]
11/17/2009 VIOL - MEANS OF EGRESS Violation Emergency lighting:

IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located]

______Fix all inoperative emergency lights.